rtr
Anti-short cycle delay: (0 to 50min) minimum interval between the compressor stop
and the following restart.
Percentage of the second and first probe for regulation: (0 to 100; 100=P1, 0=P2)
it allows to set the regulation according to the percentage of the first and second probe,
as for the following formula (rtr(P1-P2)/100 + P2).
Compressor ON time during continuous cycle: (0.0 to 24h00min, res. 10min) allows
to set the length of the continuous cycle. Compressor stays on without interruption
during CCt time. This is useful, for instance, when the room is filled with new products.
Set point for continuous cycle: (-50 to 110°C; (-58 to 230°F) it sets the set point
used during the continuous cycle.
Compressor ON time with faulty probe: (0 to 255min) time during which the
compressor is active in case of faulty thermostat probe. With Con=0 compressor is
always OFF.
SAA
SHY
Set Point for auxiliary relay: (-50 to 110.0°C; -58 to 230°F) it defines the room
temperature set point to switch auxiliary relay.
Differential for auxiliary output: (0.1 to 25.5°C; 1 to 45°F) intervention differential for
auxiliary output set point.
ACH=CL, AUX Cut in is [SAA+SHY]; AUX Cut out is SAA.
ACH=Ht, AUX Cut in is [SAA–SHY]; AUX Cut out is SAA.
CCt
ArP
Sdd
Probe selection for auxiliary: (nP; P1; P2; P3; P4) nP = no probe, the auxiliary relay
is switched only by the digital input; P1 = Probe 1 (Thermostat probe); P2 = Probe 2
(evaporator probe); P3 = Probe 3 (display probe); P4 = Probe 4.
Auxiliary relay off during defrost: (n; Y) n = the auxiliary relay operates during
defrost.
CCS
Con
Y = the auxiliary relay is switched off during defrost.
ALARMS
ALP
CoF
Compressor OFF time with faulty probe: (0 to 255min) time during which the
compressor is OFF in case of faulty thermostat probe. With CoF=0 compressor is
always active.
Probe selection for alarm: (nP; P1; P2; P3; P4) nP = no probe, the temperature
alarms are disabled; P1 = Probe 1 (Thermostat probe); P2 = Probe 2 (evaporator
probe);
DISPLAY
CF
P3 = Probe 3 (display probe); P4 = Fourth probe.
Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.
WARNING: When the measurement unit is changed the SET point and the values of
the parameters HY, LS, US, ot, ALU and ALL have to be checked and modified (if
necessary).
ALC
Temperature alarms configuration: (Ab; rE) Ab = absolute temperature, alarm
temperature is given by the ALL or ALU values. rE = temperature alarms are referred
to the set point. Temperature alarm is enabled when the temperature exceeds the
[SET+ALU] or [SET-ALL] values.
rES
Lod
Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display.
Instrument display: (P1; P2, P3, P4, SET, dtr) it selects which probe is displayed by
the instrument. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe (only
for model with this option enabled); P4 = Fourth probe, SET = set point; dtr =
percentage of visualization.
X-REP display (optional): (P1; P2, P3, P4, SET, dtr) it selects which probe is
displayed by X- REP. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe
(only for model with this option enabled); P4 = Fourth probe, SET = set point;
dtr = percentage of visualization.
Display delay: (0 to 20min00s; res. 10s) when the temperature increases, the display
is updated of 1°C or 1°F after this time.
Percentage of the second and first probe for visualization when Lod=dtr: (0 to 99;
100=P1, 0=P2) if Lod=dtr it allows to set the visualization according to the percentage
of the first and second probe, as for the following formula (dtr(P1-P2)/100 + P2).
ALU
ALL
AFH
ALd
dAo
MAXIMUM temperature alarm: (ALL to 110°C; ALL to 230°F) when this temperature
is reached the alarm is enabled, after the ALd delay time.
Minimum temperature alarm: (-50°C to ALU; -58 to ALU) when this temperature is
reached the alarm is enabled, after the ALd delay time.
Differential for temperature alarm recovery: (0.1 to 25.5°C; 1 to 45°F) intervention
differential for recovery of temperature alarm.
Temperature alarm delay: (0 to 255 min) time interval between the detection of an
alarm condition and alarm signalling.
rEd
Exclusion of temperature alarm at start-up: (0.0 to 24h00min, res. 10min) time
interval between the detection of the temperature alarm condition after instrument
power on and alarm signalling.
dLY
dtr
CONDENSER TEMPERATURE ALARM
AP2
Probe selection for temperature alarm of condenser: (nP; P1; P2; P3; P4)
nP = no probe; P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe;
P4 = Probe on Hot Key plug.
DEFROST
EdF
Defrost mode (only for controller with RTC): (rtC; in) rtC = Real Time Clock mode.
Defrost time follows Ld1 to Ld6 parameters on workdays and Sd1 to Sd6 on holidays.
in = interval mode. The defrost starts when the time idF is expired.
Defrost type: (EL; in) EL = electrical heater; in = hot gas.
Probe selection for defrost termination: (nP; P1; P2; P3; P4) nP = no probe;
P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on
Hot Key plug.
Defrost termination temperature: (-50 to 50°C; -58 to 122°F) (enabled only when
EdF=Pb) sets the temperature measured by the evaporator probe, which causes the
end of defrost.
Interval between defrost cycles: (0 to 120hours) determines the interval of time
between two defrost cycles.
(Maximum) length for defrost: (0 to 255min) when P2P=n, (not evaporator probe:
timed defrost) it sets the defrost duration. When P2P=Y (defrost end based on
temperature) it sets the maximum length for defrost.
Start defrost delay: (0 to 99min) this is useful when different defrost start times are
necessary to avoid overloading the plant.
Temperature displayed during defrost: (rt; it; SEt; dEF) rt = real temperature;
it = temperature at defrost start; SEt = set point; dEF = “dEF” label.
MAX display delay after defrost: (0 to 255min) sets the maximum time between the
end of defrost and the restarting of the real room temperature display.
Drip time: (0 to 120min) time interval between reaching defrost termination
temperature and the restoring of the control’s normal operation. This time allows the
evaporator to eliminate water drops that might have formed due to defrost.
First defrost after start-up: (n; Y) n = after the idF time, Y = immediately.
Defrost delay after continuous cycle: (0.0 to 24h00min, res. 10min) time interval
between the end of the fast freezing cycle and the following defrost related to it.
AL2
Au2
Low temperature alarm of condenser: (-50 to 110°C; -58 to 230°F) when this
temperature is reached the LA2 alarm is signalled, possibly after the Ad2 delay.
High temperature alarm of condenser: (-50 to 110°C; -58 to 230°F) when this
temperature is reached the HA2 alarm is signalled, possibly after the Ad2 delay.
Differential for temperature condenser alarm recovery: 0.1 to 25.5°C; 1 to 45°F
Condenser temperature alarm delay: (0 to 255 min) time interval between the
detection of the condenser alarm condition and alarm signalling.
tdF
dFP
AH2
Ad2
dtE
dA2
bLL
Condenser temperature alarm exclusion at start up: 0.0 to 24h00min, res. 10min.
Compressor off with low temperature alarm of condenser: (n; Y)
n
=
no:
compressor keeps on working; Y = yes, compressor is switched off till the alarm is
present, in any case regulation restarts after AC time at minimum.
Compressor off with high temperature alarm of condenser: (n; Y) n = no:
compressor keeps on working; Y = yes, compressor is switched off till the alarm is
present, in any case regulation restarts after AC time at minimum.
idF
AC2
MdF
AUXILIARY RELAY
dSd
dFd
dAd
Fdt
tbA
Alarm relay silencing (with oA2 =ALr): (n; Y) n = silencing disabled: alarm relay stays
on till alarm condition lasts; Y =silencing enabled: alarm relay is switched OFF by
pressing a key during an alarm.
Second relay configuration (1-2): (dEF; FAn; ALr; LiG; AUS; onF; db; CP2; dEF2;
HES) dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary
relay; onF = always on with instrument on; db = neutral zone; CP2 = do not select it;
dEF2 = do not select it; HES = night blind.
Alarm relay polarity: (CL; oP) it set if the alarm relay is open or closed when an alarm
occurs. CL = terminals 1-2 closed during an alarm; oP = terminals 1-2 open during an
alarm.
oA2
AoP
dPo
dAF
DIGITAL INPUTS
FANS
FnC
i1P
i1F
i2P
i2F
Digital input polarity (18-20): (oP; CL) oP = the digital input is activated by opening
Fans operating mode: (C-n; o-n; C-Y; o-Y) C-n = runs with the compressor, OFF
during defrost; o-n = continuous mode, OFF during defrost; C-Y = runs with the
compressor, ON during defrost; o-Y = continuous mode, ON during defrost.
Fans delay after defrost: (0 to 255min) interval between end of defrost and evaporator
fans start.
Temperature differential to avoid fan short cycles: (0 to 59°C; 0 to 90°F) (N.B.: if
FCt=0 function disabled) if the difference of temperature between the evaporator and
the room probes is higher than FCt value, the fans will be switched on.
Fans stop temperature: (-50 to 50°C; -58 to 122°F) setting of temperature, detected
by evaporator probe, above which fans are always OFF.
Fan ON time: (0 to 15min) with Fnc=C_n or C_Y, (fan activated in parallel with
compressor) it sets the evaporator fan ON cycling time when the compressor is off.
With Fon=0 and FoF≠0 the fan are always off, with Fon=0 and FoF=0 the fan are
always off.
Fan OFF time: (0 to 15min)
With FnC=C_n or C_Y, (fan activated in parallel with compressor) it sets the evaporator
the contact; CL = the digital input is activated by closing the contact.
Digital input configuration (18-20): (dor; dEF) dor = door switch function;
dEF = activation of a defrost cycle;
Fnd
Fct
Second digital input polarity (18-19): (oP; CL) oP = the digital input is activated by
opening the contact; CL = the digital input is activated by closing the contact.
Second digital input configuration (18-19): (EAL; bAL; PAL; dor; dEF; ES; AUS; Htr;
FAn; HdF; onF) EAL = external alarm: “EA” message is displayed; bAL = serious alarm
“CA” message is displayed; PAL = pressure switch alarm, “CA” message is displayed;
dor = door switch function; dEF = activation of a defrost cycle; ES = energy saving;
AUS = auxiliary relay activation with oA2=AUS; Htr = type of inverting action (cooling
or heating); FAn = fan; HdF = Holiday defrost (enable only with RTC); onF = to switch
the controller off.
Digital input alarm delay (18-20) when i2F=EAL or i2F=bAL: (0 to 255 min) delay
between the detection of the external alarm condition and its signalling.
When i2F= PAL, it is the interval of time to calculate the number of pressure switch
activation.
Door open signalling delay: 0 to 255 min.
Number of pressure switch activation: (0 to 15) Number of activation, during the did
interval, before signalling an alarm event (i2F=PAL).
If the nPS activation during did time is reached, switch off and on the instrument to
restart normal regulation.
Compressor status when open door: (no; FAn; CPr;F_C;) no = normal;
FAn = normal; CPr = compressor OFF, F_C = compressor OFF.
Outputs restart after doA alarm: (n; Y) n = outputs not affected by the doA alarm;
Y = outputs restart with the doA alarm.
FSt
Fon
did
FoF
FAP
fan off cycling time when the compressor is off.
With Fon=0 and FoF≠0 the fan are always off, with Fon=0 and FoF=0 the fan are
always off.
Probe selection for fan management: (nP; P1; P2; P3; P4) nP = no probe;
P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on
Hot Key plug.
doA
nPS
odc
rrd
AUXILIARY THERMOSTAT CONFIGURATION (terms. 1-2) – oA2 = AUS
ACH Kind of regulation for auxiliary relay: (Ht; CL) Ht = heating; CL = cooling.